Description
Oscillating Wave Test System Locates Partial Discharge Faults
The test system can be installed either in a cable test van in combination with a modem, centrally controlled cable test and fault location system (e. g. compact PD in a 3.5 t vehicle), or can be used as a stand-alone unit.
Features
- PD diagnosis under oscillating wave test voltage - electrical field distribution as in nominal service conditions.
- PD evaluation possibility and pattern recognition at nominal voltage level.
- Modern industrial PC for system control and user interface.
- PD level measurement according to IEC 270 at a bandwidth of 150 to 650 kHz.
- Semi and fully automatic PD analyzing software for defect location with mapping feature.
- Calculation of the cable capacitance and the tan delta value of the test object from the characteristic decrease of the voltage wave shape.
- Simple to use and easy to handle menu-driven unit for operation of the test sequence.
- Compact design; low weight.
-
Compact PD: combination of OWTS, VLF test unit and the fault location system.
System Technical Parameters(for 10kV Power Cable)
1) Capacity: ≤3uF
2) Highest test voltage: AC 25kV
3) Frequency range of damped oscillating wave: 30 ~ 300Hz
4) Frequency range of frequency conversion series resonance voltage test: 30 ~ 300Hz
5) Partial discharge test range: 10pC ~ 20nC
6) Partial discharge positioning accuracy: 1%
7) Applicable cable specifications: voltage 10kV and below, 300mm2 section cable 3km, cable 5km, cable 10km or longer cable.
Complete System Composition
1) High-voltage cable partial discharge test system software (Laptop computer)
2) AC oscillating wave high-voltage test power supply
① Output power: 15KW
② Output frequency: 30Hz-300Hz
③ Frequency resolution: 0.1HZ
④ Input power: AC220V ± 10 ﹪ or AC380V
3) Resonant reactor
① Total performance parameters (3 sections in total, can be used in series and parallel according to the site)
② Inductance: 15H / 12A
③ Working frequency: 30Hz-300Hz
④ Zui high test voltage: AC 25KV
⑤ Zui large test current: 12A
4) Dedicated PD filtering collection device
① Sampling frequency: 125MHz
② Storage depth: 64M
③ Software: professional diagnosis system
5) Excitation and oscillation wave generator
6) Partial discharge calibrator (50pC, 100pC, 200pC, 500pC, 1nC, 2nC, 5nC, 10nC, 20nC)