Description
I. Products Description and Application
HTP-2000 Frequency Response Analyzer is applied for power transformer windings deformation analyzing.The analyzer is to determine the degree of changes in internal windings of the transformer. The frequency analyzing is based on the quantity of change, magnitude and region affecting change and tendency of frequency response change which are quantized from the response changes in different frequency domains of transformer’s internal winding parameters. The measured result can help you determine whether the transformer has been severely damaged and whether a major overhaul is needed.
II. Products Key words
- Transformer Winding Deformation Tester
- Frequency Response Analyzer
- FRA Tester
- Frequency Response Analyzers for Power Transformers
- SFRA Test Set for Power and Auto-Transformers
III. Features
1. Acquisition and control using high-speed, highly integrated microprocessor.
2. Communication USB interface used between a laptop and instrument.
3. Wireless Bluetooth interface (optional) used between the laptop computer and instrument.
4. Hardware adopts dedicated DDS digital high-speed scanning technology (USA), which can accurately diagnose the faults like winding distorted, bulged, shift, tilt, inter-turn short-circuit deformation and inter-phase contact short-circuit.
5. High-speed dual-channel 16-bit A/D sampling (in field test, move tap changer, and the wave curve shows obvious change) .
6. Signal output amplitude is adjusted by software, and the peak value of amplitude is ± 10V.
7. The computer will automatically analyze the test results and generate electronic documents (Word).
8. The instrument has dual measurement features: linear frequency scanning measurement and segment frequency scanning measurement, compatible with measurement mode of two technical groups in China.
9. The amplitude-frequency characteristics are in line with the national technical specifications on amplitude-frequency characteristics tester. X-coordinate (frequency) has linear indexing and logarithmic indexing, so you can print out the curve with linear indexing and logarithmic indexing. The user can choose either according to actual needs.
10. Automatic test data analysis system.
10.1 Compare between A, B, C -phases in winding similarity comparison, and
the analysis results are:
① excellent consistency
② good consistency
③ poor consistency
④ rather poor consistency
10.2 Compare winding deformation by calling the original data and comparing it with the current data of the same phase, namely A-A, B-B, C-C, and the analysis results are:
① normal winding
② mild deformation
③ moderate deformation
④ severely deformation
11. Word electronic document can be automatically generated for saving and printing.
12. The instrument can fully meet the technical requirements of electricity standard DL/T911-2004 "Transformer winding deformation frequency response analysis".
IV. Technical Parameters
1. Scan mode:
1.1. Linear scanning distribution scanning measurement range: (10Hz) - (10MHz) 40000 scanning points, resolution 0.25kHz, 0.5kHz and 1kHz
1.2. Segment frequency scanning measurement distribution: Frequency scanning measurement range: (0.5kHz) - (1MHz), 2000 scanning points ;
- (0.5kHz) - (10kHz)
- (10kHz) - (100kHz)
- (100kHz) - (500kHz)
- (500kHz) - (1000kHz)
2. Other technical parameter
2.1. Amplitude measurement range: (-120dB) to (+20 dB)
2.2. Amplitude measurement accuracy: 0.1dB
2.3. Scanning frequency accuracy: 0.01%
2.4. Signal input impedance: 1MΩ
2.5. Signal output impedance: 50Ω
2.6. Signal output amplitude: ± 20V
2.7. Test repetition percent: 99.9%
2.8. Measuring instruments dimensions (LxWxH) 300X340X120 (mm)
2.9. Instrument’s aluminum box size (LxWxH) 310X400X330 (mm)
2.10. Overall weight: 10kg
V. Other advantages